Introduction
TpSCADALogger collects what happens inside PascalSCADA — communication, connections, scan threads, tags, events fired, security, database — and sends each message to the screen, to a file, to an event, or nowhere, according to a list of rules. A rule picks messages by source (the component name), class, category and level, so you decide, for example, that the traffic of one Modbus port goes to its own file, the S7 driver warnings go to the screen and every error also fires an event.
TpSCADALogMemo is the screen target: a read-only memo that shows the lines the rules send to the screen.
Both live on the PascalSCADA Utils palette. TpSCADALogger is in the pascalscada_common package (no LCL: it also works in services and console programs); TpSCADALogMemo is in pascalscada_hmi.
How it works
Every part of the framework posts its messages to a single, global hub. Each active TpSCADALogger gets a copy and routes it through its rules. Several loggers may exist in the same program; each one gets every message.
Logging costs nothing while nobody listens: before building a message (formatting a text, dumping a frame as hex) the code asks the hub whether some active rule wants that category and level. Posting only copies the message into the logger’s queue; the files, the screen and the event are handled by the logger’s own thread, in batches, so a communication thread never waits for the disk or the screen. Screen and event are delivered in the main thread.
Levels and categories
| Level | Use |
|---|---|
llTrace |
Everything, including the bytes of each frame. A lot of data. |
llDebug |
Details useful to understand a problem. |
llInfo |
Normal events: connected, disconnected, started. |
llWarning |
Something went wrong and was recovered (timeout, reconnection). |
llError |
Something failed. |
| Category | Messages about |
|---|---|
lcComm |
bytes sent and received by a port |
lcConnection |
opening, closing, reconnecting, timeouts |
lcProtocol |
frames and requests of a protocol driver |
lcScan |
scan and update threads, queues |
lcTag |
tag reads, writes and values |
lcEvent |
events fired |
lcThread |
threads starting and stopping |
lcSecurity |
login, logout, authorization |
lcDatabase |
the database layer |
lcHMI |
the visual controls |
lcUser |
messages of your application |
TpSCADALogger properties
| Property | Description |
|---|---|
Active |
Turns the logger on and off (default True). At design time it never runs. |
Rules |
The routing rules, evaluated in order (see below). |
Display |
The screen target: a TpSCADALogMemo or any component that implements IpSCADALogDisplay. The Object Inspector lists only those. |
LineFormat |
How a line looks. Tokens: %time%, %date%, %level%, %category%, %thread% (main, T1, T2… in the order the threads first post), %threadid% (the system id), %source%, %class%, %msg%, %data% (the payload in hex, empty when there is none). Empty restores the default. |
OnLog |
Event fired, in the main thread, for each message a rule sends to ltEvent. Gets the message fields (Entry) and the formatted Line. |
MaxFileSize |
Size limit of a log file in bytes; over it the file is renamed to .1, .2… (0 = no limit). |
MaxRotatedFiles |
How many renamed files are kept (default 5). |
FileIdleCloseMs |
A file that got nothing for this long is closed and reopened when needed (default 10 s). |
FlushIntervalMs |
How often the logger’s thread writes what is queued (default 200 ms). |
MaxQueue |
Messages the queue holds; beyond it new messages are dropped and a line N log messages dropped is logged later. Dropped counts them. |
Flush(TimeoutMs) waits until everything posted before the call has been written and, in the main thread, shown. PSLogFlushAll does the same for every logger.
The default line looks like this:
2026-11-17 14:03:22.417 [WARN ] [connection] T2 Form1.ModBusTCP1 (TModBusTCPDriver): timeout, reconnecting
2026-11-17 14:03:22.419 [TRACE] [comm] T2 Form1.TCP_UDPPort1 (TTCP_UDPPort): TX | 00 01 00 00 00 06 01 03 00 00 00 0A
Rules
A message matches a rule when all of these hold:
| Property | Matches when |
|---|---|
Enabled |
the rule is enabled. |
MinLevel |
the message level is this one or higher (default llInfo). |
Categories |
the message category is in the set (default: all). |
SourceMask |
the source matches the mask. The source is the component path, like Form1.ModBusTCP1. Accepts * and ?, ignores case, and takes several masks separated by ;. Empty means everything. |
ClassMask |
the class of the source or one of its ancestors matches the mask — TProtocolDriver matches every driver. Same syntax as SourceMask. |
And then:
| Property | Effect |
|---|---|
Targets |
Where it goes: ltScreen, ltFile, ltEvent, any combination. Empty drops the message. |
FileName |
The file for ltFile. Accepts %date%, %source%, %class%, %category% and %level%, so one rule can write one file per day, per source or per class. A relative path is relative to the executable’s folder; missing folders are created. |
StopProcessing |
When the rule matches, the following rules are not evaluated. With empty Targets it makes an exclusion. |
When several rules match, the message goes to all their targets; two rules on the same file write the line once.
Examples:
| Goal | Rule |
|---|---|
| Errors and warnings of everything on the screen | MinLevel = llWarning, Targets = [ltScreen] |
| Traffic of each port in its own daily file | Categories = [lcComm], MinLevel = llTrace, Targets = [ltFile], FileName = logs/%source%-%date%.log |
| Everything from the S7CommPlus driver in one file | ClassMask = TS7CommPlusDriver, MinLevel = llDebug, Targets = [ltFile], FileName = logs/s7plus.log |
| Ignore one noisy component | first rule: SourceMask = Form1.Debug*, Targets = [], StopProcessing = True |
TpSCADALogMemo
A memo set up for logs: read-only, no word wrap, scroll bars. Link it to the logger’s Display.
| Property | Description |
|---|---|
MaxLines |
Lines kept; the oldest go first (default 1000, 0 = no limit). |
AutoScroll |
Keeps the last line in view when new lines come (default True). Turn it off to read calmly. |
A monospaced font keeps the columns aligned. To show the log somewhere else (a list, a grid, a status bar) use the OnLog event, or write a component that implements IpSCADALogDisplay (one method, AddLogLines(Lines: TStrings), called in the main thread).
What PascalSCADA posts
| Who | Category / level | Messages |
|---|---|---|
| every communication port | lcComm / llTrace |
TX 12/12 iorOK, RX 10/10 iorOK, with the bytes as payload, in the order the port did them. |
lcComm / llWarning |
read failed: iorTimeOut, write failed: … |
|
lcConnection / llInfo |
port started, port stopped |
|
lcConnection / llError |
open failed, close failed, with the operating system error |
|
lcConnection / llWarning |
connection lost |
|
TTCP_UDPPort |
lcConnection / llInfo |
connected, reconnecting (llDebug: closing the socket) |
TS7CommPlusDriver |
lcProtocol / llDebug |
the same messages as OnDebug (its connection’s included), with the driver as the source |
TOPCUADriver |
lcProtocol / the message’s level |
the same messages as OnLog; the driver’s LogLevel still decides what the library reports |
| every protocol driver | lcThread / llDebug |
TScanThread started, TScanUpdate finished… (llError when an exception stops a thread) |
lcScan / llError |
an exception during the scan (scan read raised …, tag update raised …) — these used to be silently swallowed |
|
| every tag | lcTag / llDebug |
scan write requested: [12.5], scan write ok (sync for synchronous writes) |
lcTag / llWarning |
scan write failed: ioTimeOut; read failed: ioCommError once when reading starts failing, and reading again (llInfo) when it comes back |
|
lcTag / llTrace |
every read (scan read ioOk) and every value change (value changed: 12.5 (raw 125)) |
|
lcEvent / llTrace |
each event assigned and fired: OnValueChange, OnValueChangeFirst, OnAsyncValueChange, OnReadOk, OnReadFail, OnWriteOk, OnWriteFail, OnUpdate |
|
lcEvent / llError |
an exception raised while the tag was being updated — usually in your OnValueChange. The other tags of the batch are still updated. |
|
| user managers | lcSecurity / llInfo |
login: fabio (password) or (chip card), logout: fabio, access to "valves" granted to maria (password) (llDebug when the logged user already has it) |
lcSecurity / llWarning |
login failed: fabio (password), login blocked for 30000 ms after 3 failures, access to "valves" denied to maria. Passwords are never logged. |
|
| HMI controls that write to a tag | lcHMI / llInfo |
wrote 1 to Form1.Valve1 (user fabio), with the control as the source — an audit trail of the operator’s actions (THMIEdit, THMICheckBox, THMIButton, THMIRadioGroup, THMITrackBar, THMIComboBox, THMIUpDown, THMIScrollBar) |
lcHMI / llWarning |
write of 10 to Form1.Valve1 refused (user fabio): <reason>, e.g. out of the tag limits |
|
THMIDBConnection |
lcDatabase / llInfo |
connected (postgresql host/db), disconnected (llError when it fails) |
lcDatabase / llDebug |
SQL ok (12 rows): select …, transaction committed (3 statements) |
|
lcDatabase / llWarning, llError |
SQL refused (ReadOnly): …, transaction rolled back …, SQL failed: <error> followed by the SQL, commit/rollback failed |
Connection messages carry the port in parentheses: (192.168.0.10:502 TCP), (COM1 19200 8N1). The ports’ LogIOActions/LogFile and the drivers’ OnDebug/OnLog keep working as before. A driver’s threads start before the driver gets its name (the form sets the properties afterwards), so their started messages show the class, as in Form1.<TModBusTCPDriver>; everything after that shows the name. lcTag and lcEvent at llTrace produce a line per tag per scan: narrow those rules with SourceMask. lcDatabase at llDebug writes the SQL text, values included: keep it out of files other people read if your statements carry sensitive data.
Logging from your code
uses pscadalog; PSLog(Self, lcUser, llInfo, 'batch started'); PSLogFmt(Self, lcUser, llWarning, 'tank %d above %f', [TankNo, Level]); //build expensive messages only when someone wants them if PSLogWants(lcComm, llTrace) then PSLog(Self, lcComm, llTrace, 'frame', FrameBytes);
Self (the sender) becomes the source and the class of the message; it may be nil. PSLog may be called from any thread.
Programs without the LCL
Files work in any program. The screen and the OnLog event reach the main thread through TThread.Queue, so a console program or service must call CheckSynchronize from time to time (an LCL application already does it).
Related examples
examples/laz_pscadalogger— a logger with three rules (screen, one file per category and day, an event counting the errors), aTpSCADALogMemo, a button to post messages of any level and category and a burst of four threads posting at the same time.