Introduction

TISOTCPDriver speaks S7comm over ISO-on-TCP (RFC 1006, TCP port 102) — the same protocol STEP 7, TIA Portal and LibNodave use to read and write the memory of a Siemens PLC. The driver is a Pascal rewrite of LibNodave’s ISOTCP by Thomas Hergenhahn: it depends on no DLL or external library.

It talks to:

  • S7-300, S7-400, ET200S/ET200SP with an Ethernet CPU or CP;
  • S7-1200 and S7-1500 — after enabling PUT/GET access and turning off optimized access on the DBs (see Preparing the PLC);
  • S7-200 through a CP 243-1 (ConnectionWay = ISOTCP_VIA_CP243);
  • LOGO! 0BA7/0BA8 (LOGO! 7 and 8), which exposes its V area as DB1;
  • any S7comm-compatible simulator or gateway (PLCSIM with NetToPLCSim, Snap7 server, and so on).

It does not talk to the S7-1200/1500 through their native protocol (S7CommPlus, which TIA Portal uses for symbolic access) — that is what TS7CommPlusDriver is for. ISOTCP remains the simplest option for those PLCs when you control the TIA project and can turn optimized access off.

Required components
  1. A TTCP_UDPPort with Host = PLC IP address, Port = 102 (default) and PortType = ptTCP. See Communication ports.
  2. A TISOTCPDriver with CommunicationPort pointing to the port.
  3. The tags (TPLCTagNumber, TPLCBlock, TPLCStruct, TPLCString) with ProtocolDriver pointing to the driver.

The fastest way to get to step 3 is to right-click the TISOTCPDriver and choose Tag Builder (see below).

Driver properties
Property Default Description
CommunicationPort – The TTCP_UDPPort used by the driver.
PLCRack 0 CPU rack.
PLCSlot 0 CPU slot.
PLCStation 2 Station address. Only meaningful on MPI/PROFIBUS networks behind a gateway; on Ethernet leave the default.
ConnectionWay ISOTCP ISOTCP for a direct connection to the CPU/Ethernet CP; ISOTCP_VIA_CP243 for an S7-200 behind a CP 243-1.
ISOTCPConnType ctOP Connection type the driver announces to the PLC: ctPG (programming device), ctOP (operator panel) or ctBasic (other). The PLC reserves resources per type; if every OP connection is in use, switch to ctBasic.
ForcePDUSize pduAuto Negotiated PDU size. pduAuto asks for the largest the PLC accepts; force pdu240 for old PLCs or LOGO!, which do not negotiate correctly.
ReadOnly False When True the driver refuses every write (ioReadOnlyProtocol). Handy for a monitoring screen that must never change the process.
ReadSomethingAlways True Keeps the connection alive by reading some tag every cycle even when none needs updating.

One ISOTCP connection talks to one PLC. For that reason the PLCRack, PLCSlot and PLCStation properties of the tags are ignored: what counts is the driver’s configuration. To talk to two PLCs, use two ports and two drivers.

Rack/slot values that work in most cases:

CPU PLCRack PLCSlot
S7-300 (CPU with built-in PN or CP 343-1) 0 2
S7-400 0 physical slot of the CPU (usually 2 or 3)
S7-1200 / S7-1500 0 0 (1 also works on the 1200)
ET200S / ET200SP CPU 0 2 (ET200S) / 0 (ET200SP)
S7-200 via CP 243-1 0 0
LOGO! 7 / 8 0 0 (see Preparing the PLC)

From code, UpdatePLCAddress(Rack, Slot, Station) changes the three at once without restarting the connection three times.

Preparing the PLC

S7-300 / S7-400: nothing beyond having the IP address configured. If the CPU has a write-protection password, the driver reads but does not write.

S7-1200 / S7-1500 (in TIA Portal):

  1. In the CPU properties → Protection & Security → Connection mechanisms: tick Permit access with PUT/GET communication from remote partner.
  2. In every DB PascalSCADA will access, untick Optimized block access (DB properties → Attributes) and recompile. An optimized DB has no absolute addresses, and ISOTCP addresses by byte only.
  3. If the CPU protection level is Full access, nothing else. With Read access the driver only reads; with HMI access or No access the connection is refused.

LOGO! 7 / 8 (in LOGO!Soft Comfort): under Tools → Ethernet connections, add a server connection with local TSAP 20.00 and remote TSAP 10.00, or tick Allow all connections. The V area (VB/VW/VD) shows up to PascalSCADA as DB1 (MemReadFunction = 4, MemFile_DB = 1); the M memories as area M (MemReadFunction = 3). The examples/demo_logo8 example shows this, with ForcePDUSize = pdu240 and PLCStation = 0.

S7-200: use ConnectionWay = ISOTCP_VIA_CP243 and configure a connection in the CP 243-1 with the STEP 7-Micro/WIN wizard. The V area is MemReadFunction = 4 with MemFile_DB = 1.

Addressing memory

Every S7 address is made of an area, a DB number (DB area only), a byte address and the variable type. On the tag this becomes:

Tag property Fill with
MemReadFunction Area code (table below).
MemFile_DB DB number, when the area is 4. Ignored otherwise.
MemAddress Address of the first byte (the number after IB, MW, DBD…).
TagType Variable type (table further below).
MemWriteFunction, MemSubElement, PLCRack/Slot/Station Not used. Leave at zero.

Area codes for MemReadFunction:

Code Area CPUs Note
1 I — digital inputs (process image) all
2 Q — digital outputs (process image) all
3 M — flags/markers all
4 DB — data block 300/400/1200/1500; V on S7-200 and LOGO! Fill MemFile_DB.
5 C — counters 300/400 TagType = pttWord.
6 T — timers 300/400 TagType = pttWord.
7 SM — special memory S7-200
8 AI — analog inputs S7-200 TagType = pttWord.
9 AQ — analog outputs S7-200 TagType = pttWord.
10 C — counters S7-200 TagType = pttWord.
11 T — timers S7-200 TagType = pttWord.
12 PIW — peripheral input 300/400 TagType = pttWord. Reads the value straight from the module, bypassing the process image.

S7 data types and the matching TagType:

PLC type Bytes TagType SwapBytes SwapWords SwapDWords
BOOL – pttByte on the tag + one TTagBit per bit
BYTE, CHAR, USINT 1 pttByte
SINT 1 pttShortInt
WORD, UINT, S5TIME, DATE 2 pttWord ✔
INT 2 pttSmallInt ✔
DWORD, UDINT, TIME_OF_DAY 4 pttDWord ✔ ✔
DINT, TIME 4 pttLongInt ✔ ✔
REAL 4 pttFloat ✔ ✔
LINT, LTIME 8 pttInt64 ✔ ✔ ✔
ULINT, LWORD 8 pttQWord ✔ ✔ ✔
LREAL 8 pttDouble ✔ ✔ ✔
STRING[n] n + 2 TPLCString with StringType = stSIEMENS

Siemens PLCs store values in big-endian and PascalSCADA assembles bytes in machine order (little-endian). So everything wider than one byte needs the Swap* flags set as in the table — without them an INT = 1 shows up as 256 and a REAL becomes an absurd number. The Tag Builder sets the right swaps for you.

Examples:

S7 address MemReadFunction MemFile_DB MemAddress TagType Swaps
IB3 1 0 3 pttByte –
Q0.5 2 0 0 pttByte + TTagBit with StartBit = EndBit = 5 –
MW10 3 0 10 pttWord B
MD100 (as REAL) 3 0 100 pttFloat B + W
DB5.DBW20 4 5 20 pttSmallInt B
DB5.DBD24 (as DINT) 4 5 24 pttLongInt B + W
DB10.DBB0 to DBB49 4 10 0 TPLCBlock pttByte, Size = 50 –
DB12 STRING[30] at DBB8 4 12 8 TPLCString, StringSize = 30, stSIEMENS –
VW6 (LOGO!/S7-200) 4 1 6 pttSmallInt B
T5 (S7-300) 6 0 5 pttWord B
Bits

PascalSCADA’s ISOTCP reads and writes by byte. For a BOOL (an input, an output, a bit of a DB), create a TPLCTagNumber with TagType = pttByte pointing to the byte that holds the bit and a TTagBit for each bit of interest (StartBit = EndBit = bit number). Writing to the TTagBit reads the current byte, changes only that bit and writes the byte back.

For many bits in the same byte, right-click the tag and choose Map bits: it creates the eight TTagBits at once. The examples/laz_isotcp_mapping_bits_from_other_tag example does this with DB1.DBB0.

Blocks, structures and strings
  • A TPLCBlock reads Size consecutive variables of the same type in one request — an array of REAL in a DB, for instance (TagType = pttFloat, Size = number of elements, MemAddress = first byte). The swaps apply to the whole block.
  • A TPLCStruct reads Size consecutive bytes, and each TPLCStructItem/TPLCStructString interprets a slice with its own type and swaps. It is the natural way to map a DB with mixed fields or a UDT — see the example in Tags.
  • A TPLCString with StringType = stSIEMENS reads a STRING[n]: the two header bytes (maximum and current length) are handled by the driver. Use stC only for zero-terminated CHAR arrays.

The driver automatically merges neighbouring tags of the same area and RefreshTime into one request, within the negotiated PDU size. With pduAuto on a modern CPU up to 1920 data bytes fit in one message; on an old S7-300 or LOGO!, 240. If the tags’ AvgUpdateRate stays well above RefreshTime, the PLC cannot keep up — raise the RefreshTime of the less critical tags or group them into blocks.

Tag Builder

Right-click the TISOTCPDriver → Tag Builder opens the Siemens S7 Tag builder wizard:

  1. Choose the area (inputs, outputs, flags, DB, counters, timers, S7-200 areas…), the kind of tag to create (separate TPLCTagNumbers, one TPLCBlock, or TPLCStruct) and the scan time.
  2. For separate tags or a block: give the data type, start address, count and DB. The wizard sets SwapBytes/SwapWords according to the type.
  3. For structures: build the item list (name, type, swap, scan) on the Items declaration tab; the wizard computes the offsets and can generate N identical structures in sequence (useful for UDT arrays).

The created components appear on the form/datamodule with ProtocolDriver already linked.

Step-by-step example

Read the temperature DB1.DBD0 (REAL) and write the setpoint DB1.DBW4 (INT) of an S7-1200 at 192.168.0.10:

  1. In TIA Portal: enable PUT/GET, untick Optimized block access on DB1, compile and download.
  2. Drop a TTCP_UDPPort: Host = 192.168.0.10, Port = 102, Active = True.
  3. Drop a TISOTCPDriver: CommunicationPort = TCP_UDPPort1, PLCRack = 0, PLCSlot = 0.
  4. Drop a TPLCTagNumber named Temperature: ProtocolDriver = ISOTCPDriver1, MemReadFunction = 4, MemFile_DB = 1, MemAddress = 0, TagType = pttFloat, SwapBytes = True, SwapWords = True.
  5. Drop another named Setpoint: same, with MemAddress = 4, TagType = pttSmallInt, SwapBytes = True.
  6. Link a THMILabel to Temperature and a THMIEdit to Setpoint. Run.

The same from code, for those who create the components at run time:

uses tcp_udpport, ISOTCPDriver, PLCTagNumber, ProtocolTypes;

var
  Port: TTCP_UDPPort;
  Drv: TISOTCPDriver;
  Temp: TPLCTagNumber;
begin
  Port := TTCP_UDPPort.Create(Self);
  Port.Host := '192.168.0.10';
  Port.Port := 102;

  Drv := TISOTCPDriver.Create(Self);
  Drv.CommunicationPort := Port;
  Drv.PLCRack := 0;
  Drv.PLCSlot := 0;

  Temp := TPLCTagNumber.Create(Self);
  Temp.MemReadFunction := 4;   // DB
  Temp.MemFile_DB := 1;
  Temp.MemAddress := 0;
  Temp.TagType := pttFloat;
  Temp.SwapBytes := True;
  Temp.SwapWords := True;
  Temp.RefreshTime := 500;
  Temp.ProtocolDriver := Drv;  // last

  Port.Active := True;
end;

More examples in the repository: examples/laz_isotcp_demonstration (DB with block, string and bits), examples/laz_isotcp_hourmeter (hour meter with writes), examples/laz_isotcp_performance (update-rate measurement) and examples/demo_logo8.

Common problems
Symptom Likely cause
Port opens (Active = True) but no tag updates; LastSyncReadStatus = ioConnectPLCFailed Wrong rack/slot, or S7-1200/1500 without PUT/GET enabled, or protection level No access.
Port does not open (OnCommPortOpenError) Wrong IP, port 102 blocked by a firewall, or the PLC already reached its connection limit (change ISOTCPConnType).
Tags of one specific DB return ioIllegalMemoryAddress / ioObjectNotExists The DB does not exist, is shorter than the requested address, or (1200/1500) still has Optimized block access on.
Absurd 16/32-bit values (1 becomes 256, a REAL becomes 1E-40) Missing SwapBytes/SwapWords.
Writes fail with ioReadOnlyProtocol or ioObjectAccessNotAllowed ReadOnly = True on the driver, or the CPU is write-protected/password protected.
Works on an S7-300 but not on a LOGO! Force ForcePDUSize = pdu240 and check the server connection TSAP in LOGO!Soft.
Timers/counters read as zero TagType must be pttWord on those areas.
Related examples