Introduction
TOPCUADriver is an OPC UA client. It reads and writes the variables of any OPC UA server: the S7-1200/1500 and PLCSim servers, the server built into other PLC brands, an OPC UA gateway, a SCADA that exposes its tags, or a server written with open62541.
The protocol itself is handled by open62541 1.5 (the C library), through the Pascal binding fpopen62541, which ships with PascalSCADA in src/external/fpopen62541. The library is loaded at run time, on the first connection only: a program that does not use the driver does not need it.
| Servers | any OPC UA server reachable by opc.tcp:// |
| Addressing | the NodeId of the variable: ns=3;s="DB1"."Speed", nsu=urn:my:server;i=1001 |
| Values | subscriptions (the server reports the changes) or polling in batches |
| Security | None, Sign, SignAndEncrypt; anonymous or user/password |
| Tag Builder | browses the server and creates the tags |
One driver talks to one server. To read two servers, use two
TOPCUADriver.
Required components
- A
TOPCUADriver(unitOPCUADriver) withEndpointUrl= the server address, for exampleopc.tcp://192.168.0.10:4840. 4840 is the standard OPC UA port. There is no communication port component: the library opens the connection itself. - The tags (
TPLCTagNumber,TPLCBlock,TPLCString) withProtocolDriverpointing to the driver andLongAddressholding the NodeId of the variable (see Addressing). - The open62541 1.5 library on the machine that runs the program (see the next section).
The fastest way to get to step 2 is the Tag Builder (see below), which browses the server and creates the tags.
The open62541 library
The driver needs open62541 1.5 built as a shared library with encryption (UA_ENABLE_ENCRYPTION=OPENSSL); a library of another version, or without encryption, is refused at load time with a message saying why.
- Linux: build it from the sources and install it in the system:
git clone --branch v1.5.10 --recurse-submodules https://github.com/open62541/open62541.git
cmake -S open62541 -B open62541/build -DCMAKE_BUILD_TYPE=Release -DBUILD_SHARED_LIBS=ON \
-DUA_ENABLE_ENCRYPTION=OPENSSL
cmake --build open62541/build -j
sudo cmake --install open62541/build && sudo ldconfig
- Windows:
libopen62541.dll, of the same bitness as the program, next to the executable (and next tolazarus.exeto use the Tag Builder in the IDE). The workflowBuildOpen62541v1.5.ymlof fpopen62541 builds it for Win32 and x64 with OpenSSL linked inside, so no OpenSSL DLL is needed.
With LibraryName empty, the driver looks for the library in this order: the system name (libopen62541.so / libopen62541.dll), libopen62541.so.1.5 (Linux), and the same names in the folder of the executable — so the library can ship with the application. LibraryName with a path or a name skips the search. When nothing is found, LastError lists every place tried.
Preparing the server
On an S7-1200/1500 (or PLCSim Advanced), in TIA Portal:
- CPU properties → OPC UA → Server: tick Activate OPC UA server. The endpoint shown there is the
EndpointUrl(port 4840 by default). The CPU also needs an OPC UA runtime license selected under Runtime licenses. - Only the variables marked Accessible from HMI/OPC UA (and Writable from HMI/OPC UA to write) are published.
- Server → Security: the security policies the server accepts and whether guest (anonymous) access is enabled. Without No security in the list, the driver must use Sign or SignAndEncrypt and the server must trust the client certificate (see Security).
The NodeIds of the variables of a Siemens CPU look like ns=3;s="DB1"."Speed" — with the quotation marks.
Driver properties
| Property | Default | Description |
|---|---|---|
EndpointUrl |
– | Server address, opc.tcp://host:port. |
Username / Password |
empty | Empty Username: anonymous session. |
SecurityMode |
osmNone |
osmNone, osmSign (signed) or osmSignAndEncrypt (signed and encrypted). |
SecurityPolicy |
ospAuto |
ospAuto takes the best one the server offers for the mode; or a fixed one: ospBasic256Sha256, ospAes128Sha256RsaOaep, ospAes256Sha256RsaPss, ospBasic256, ospBasic128Rsa15. |
CertificateFile / PrivateKeyFile |
empty | Client certificate and key (DER or PEM). Empty: one is generated on the first secure connection and kept in CertificateDir. |
CertificateDir |
config folder of the app + opcua-pki |
Where the generated certificate is kept: own/pascalscada-client.der and private/pascalscada-client.key. |
TrustListDir |
empty | Folder with the certificates (.der, .pem, .crt, .cer) of the trusted servers. Empty accepts any server. |
ApplicationUri / ApplicationName |
urn:pascalscada:opcua:client / PascalSCADA OPC UA Client |
How the client introduces itself. The URI goes in the generated certificate. |
AllowUnencryptedPassword |
False |
Lets the password travel on a channel without encryption (osmNone). Keep it off outside of tests. |
Timeout |
5000 | Timeout of a request, in ms. |
SessionTimeout |
60000 | Session lifetime asked to the server, in ms. |
ReconnectInterval |
3000 | Wait between two connection attempts, in ms. |
UseSubscriptions |
True |
Values by subscription; False reads the tags periodically (see Subscriptions or polling). |
PublishingInterval |
100 | How often, in ms, the server sends the changes of the subscription. |
MaxItemsPerRequest |
500 | Most variables in one read, write or monitored item request; more are split in several requests. |
LibraryName |
empty | Name or path of the library; empty searches it (see above). |
LogLevel / OnLog |
ollWarning |
Messages of the driver and of the library. OnLog is called from the driver threads: do not touch the form inside it. |
ReadOnly |
False |
No write reaches the server. |
Methods: Connected, LastError, ListTags, Browse, GetVariableInfo, GetServerCertificates, GetClientCertificate (see Browsing from code).
Addressing
LongAddress is the NodeId of the variable, as text:
ns=3;s="DB1"."Speed" // namespace index + string identifier (Siemens)
ns=2;i=1001 // numeric identifier
ns=2;g=09087e75-8e5e-499b-954f-f2a9603db28a // GUID
nsu=http://www.siemens.com/simatic-s7-opcua;s="DB1"."Speed" // namespace URI
ns= uses the index of the namespace in the server; nsu= uses its URI, which does not change if the server reorders its namespaces — the Tag Builder writes nsu= by default. Namespace 0 is the standard one: i=2258 is the current time of the server.
A | followed by an IndexRange picks elements of an array: ns=3;s="DB1"."Arr"|4 is element 4, ns=3;s="DB1"."Arr"|0:9 the first ten. Indexes start at 0, whatever the array bounds are in the PLC program.
Tags and types
The server tells the type of each variable, so the driver converts the value itself: keep TagType = pttDefault, with no swaps and no scale tricks.
| OPC UA type | Tag | Value |
|---|---|---|
| Boolean | TPLCTagNumber |
0 / 1; writing any value other than 0 writes true |
| SByte, Byte, Int16, UInt16, Int32, UInt32, Int64, UInt64 | TPLCTagNumber |
the number. 64-bit integers above 2^53 lose precision (the tag value is a Double). |
| Float, Double | TPLCTagNumber |
the number |
| DateTime | TPLCTagNumber |
a TDateTime in local time (format it with FormatDateTime) |
| Enumeration, StatusCode | TPLCTagNumber |
its numeric value |
| array of any of the above | TPLCBlock (Size = number of elements) |
one value per element |
| String, LocalizedText, QualifiedName, ByteString, Guid, NodeId | TPLCString (StringType = stC) |
the text in UTF-8 |
A write that does not fit the type of the variable (300 into a Byte, a text that is not a number into a numeric variable) is refused with ioIllegalValue, without reaching the server. Writing one element of a TPLCBlock writes only that element (by IndexRange); if the server does not accept an IndexRange write, the driver reads the array, changes the element and writes it whole.
Structures (user data types) are not decoded: address their members one by one.
Subscriptions or polling
With UseSubscriptions = True (the default) the driver creates one subscription and a monitored item per variable: the server samples the variable every RefreshTime of the tag and sends only what changed, at most every PublishingInterval. A tag with RefreshTime = 0 asks the server for its fastest sampling. Several tags on the same NodeId share one monitored item with the fastest RefreshTime.
With UseSubscriptions = False the variables are read periodically, each at its RefreshTime, in batches of up to MaxItemsPerRequest. Use it with servers that do not support subscriptions, or to have every value read at a fixed rate even when it does not change.
When the connection drops, every tag gets the error; the driver tries again every ReconnectInterval and, once connected, recreates the subscription by itself.
Security
- None (
osmNone): nothing is signed or encrypted. A password is only sent this way withAllowUnencryptedPassword = True. - Sign / SignAndEncrypt: the messages are signed (and encrypted). Both sides present certificates and each one has to trust the other:
- The server trusts the client. With
CertificateFileempty the driver generates a self-signed certificate on the first secure connection and keeps it inCertificateDir. Giveown/pascalscada-client.derto the server as a trusted client — in TIA Portal it goes to the trusted clients of the OPC UA server (Server → Security → Secure channel), unless the server is set to accept client certificates automatically; other servers usually keep a refused certificate in a rejected folder, to be moved to trusted. The Tag Builder has an Export client certificate button for this. The certificate is kept, so it is trusted once. - The client trusts the server. With
TrustListDirempty, any server is accepted. To accept only known servers, put their certificates in that folder — the Trust server certificate button of the Tag Builder saves the one of the current server there.
- The server trusts the client. With
- User and password:
UsernameandPassword. A wrong password ends withioAuthError.
Tag Builder
Right-click the TOPCUADriver → Tag Builder opens OPC UA Tag Builder.
- Press Browse: the tree shows the Objects folder of the server; folders and objects expand on demand.
- Select the variables (Ctrl/Shift for several). Set Scan (the
RefreshTimeof the new tags) and an optional name Prefix. Address with the namespace URI (nsu=) chooses betweennsu=(default) andns=addresses. - OK creates one tag per variable:
TPLCTagNumberfor a numeric scalar,TPLCBlock(withSizealready set) for a numeric array andTPLCStringfor a text. Structures and other types without an equivalent are skipped and counted in a message.
The buttons Trust server certificate (saves the server certificate in TrustListDir) and Export client certificate are in the same window (see Security).
Browsing from code
var
tags: TPLCTagInfoArray;
info: TOPCUAVariableInfo;
i: Integer;
begin
if OPCUADriver1.ListTags(tags) = ioOk then // every variable under Objects
for i := 0 to High(tags) do
Memo1.Lines.Add(tags[i].Path + ' ' + tags[i].NativeType);
if OPCUADriver1.GetVariableInfo('ns=3;s="DB1"."Speed"', info) = ioOk then
Memo1.Lines.Add(Format('%s rank %d', [info.DataTypeName, info.ValueRank]));
end;
ListTags walks the Objects folder recursively, up to 12 levels and 20000 variables (Path is the NodeId with nsu=, ready for LongAddress); Browse returns the children of one node; GetVariableInfo gives the type, the ValueRank (-1 scalar, ≥ 0 array), the dimensions and the access level of a variable. They connect by themselves when needed.
Step-by-step example
- Drop a
TOPCUADriverand setEndpointUrl(e.g.opc.tcp://192.168.0.10:4840). - Right-click it → Tag Builder → Browse, select some variables and press OK.
- Drop HMI controls (
THMILabel,THMIEdit,THMITrackBar, …) and point theirPLCTagat the new tags. - Run. The values show up; typing in a
THMIEditwrites back to the server.
To try it without a server, examples/laz_opcua_hmi starts a small test server inside the program.
Errors
The OPC UA status codes become the usual TProtocolIOResult of the tags:
| Status code (examples) | Result |
|---|---|
| Good, Uncertain | ioOk |
| BadNodeIdUnknown, BadNodeIdInvalid, BadNotFound | ioObjectNotExists |
| BadUserAccessDenied, BadNotReadable, BadNotWritable | ioObjectAccessNotAllowed |
| BadTypeMismatch, BadOutOfRange | ioIllegalValue |
| BadIndexRangeInvalid, BadIndexRangeNoData | ioIllegalMemoryAddress |
| BadTimeout | ioTimeOut |
| BadIdentityTokenInvalid/Rejected, wrong password | ioAuthError |
| BadCertificate…, BadSecurityChecksFailed, BadConnectionRejected | ioConnectPLCFailed |
| connection or session lost | ioCommError |
Common problems
| Symptom | Likely cause |
|---|---|
LastError: libopen62541 1.5 not found |
The library is not installed or not next to the executable; see The open62541 library. |
| is not an open62541 1.5 library / was built without encryption | A library of another version, or built without UA_ENABLE_ENCRYPTION. |
Every tag ioConnectPLCFailed with Sign/SignAndEncrypt |
The server does not trust the client certificate yet: export it and add it to the server’s trusted list. Or TrustListDir is set and does not hold the server certificate. |
Every tag ioAuthError |
Wrong user/password, or the server does not allow anonymous access. |
ioObjectNotExists on a Siemens variable |
NodeId without the quotation marks (s="DB1"."Speed"), or the variable is not Accessible from HMI/OPC UA. |
Writes refused (ioObjectAccessNotAllowed) |
The variable is not Writable from HMI/OPC UA, the user may not write, or ReadOnly = True. |
| A fast signal is seen late | Lower RefreshTime (sampling) and PublishingInterval, or use polling. |
| A tag reads another variable (or none) after the server was updated | The server reordered its namespaces and the ns= index changed: use nsu= addresses. |
Related examples
examples/laz_opcua_client— connects to any endpoint, lists the variables of the server, monitors and writes the ones picked; Test server starts a local server to try it without a PLC.examples/laz_opcua_hmi— an HMI screen made only on the form:TOPCUADriver, tags and HMI controls set at design time, with the instructions on the form.