Introduction
In PascalSCADA a tag is the component that represents a memory (or a set of memories) of a device: a holding register of a Modbus drive, a byte of a DB in a Siemens PLC, a controller tag in a Rockwell PLC. The tag sits in the middle of the communication chain:
Communication port → Protocol driver → Tag → HMI control / your code
The port carries bytes, the driver speaks the device’s protocol, and the tag tells the driver what to read and write, keeps the last value read and notifies whoever depends on it when that value changes. The HMI controls (THMIEdit, THMILabel, THMICheckBox…) never talk to the driver: they are linked to a tag through their PLCTag property and react to its changes. One tag can feed as many controls as you want.
All tags live on the PascalSCADA Tags palette and descend from TTag → TPLCTag. From there they split into two groups:
- Numeric tags (
TPLCNumber): expose a singleDoublevalue in theValueandValueRawproperties. These areTPLCTagNumber,TPLCBlockElement,TPLCStructItem,TTagBitandTNumericExprTag. - Block tags (
TTagBlock): map several consecutive memories in a single request. These areTPLCBlock,TPLCStructandTPLCString.
The table below summarizes when to use each one:
| Component | Use it when… |
|---|---|
TPLCTagNumber |
you need one numeric value, addressed and read on its own. |
TPLCBlock + TPLCBlockElement |
you need several consecutive values of the same type (e.g. 20 registers starting at address 100). The block issues a single request; each element exposes one item of the block as a numeric tag. |
TPLCStruct + TPLCStructItem + TPLCStructString |
you need several values of different types that sit together in memory (a PLC STRUCT/UDT, a Siemens DB mixing bytes, words and reals). |
TPLCString |
you need to read or write a text. |
TTagBit |
you need one or more bits of another numeric tag, without extra communication. |
TNumericExprTag |
you need a value computed from other tags, with no communication of its own. |
How a tag is read and written
Every communication tag has four operations available from code:
| Method | Direction | Behaviour |
|---|---|---|
ScanRead |
read | Asynchronous. Queues a read request on the driver and returns at once. The value arrives later, in the OnValueChange/OnUpdate events. |
Read |
read | Synchronous. Blocks until the driver answers (or fails). On return Value is already updated and LastSyncReadStatus tells the result. |
ScanWrite |
write | Asynchronous. Queues the write and returns. The result goes to LastASyncWriteStatus and to the OnWriteOk/OnWriteFail events. |
Write |
write | Synchronous. Blocks until the write is confirmed. |
In practice you rarely call these methods. Day-to-day behaviour is governed by a few properties:
AutoRead— whenTrue(default) the driver includes the tag in its scan cycle and reads it automatically everyRefreshTimemilliseconds. WhenFalsethe tag is only read when you callReadorScanRead.RefreshTime— update period of the tag, in milliseconds (default 1000). Tags on the same driver with the sameRefreshTimeand neighbouring addresses are grouped by the driver into a single request whenever the protocol allows it, so there is no penalty in using many small tags; useTPLCBlockwhen you want to guarantee that the data arrives together, as a single snapshot.AutoWrite— whenTrue(default) every assignment toValue(from code or from an HMI control) produces a write to the device. WhenFalsethe assignment only changes the value in memory; it goes to the device when you callWriteDirect(blocks) orWrite/ScanWrite.SyncWrites— whenTrue, writes triggered byAutoWriteare synchronous (Write) instead of asynchronous (ScanWrite). Leave itFalseunless the code that assigned the value must be sure it has already reached the device.
The rule of thumb is: leave
AutoReadandAutoWriteatTrueand call nothing — the driver does the work. TurnAutoReadoff only for tags that must be read at a specific moment (a recipe loaded on demand, for instance) and callReadat that moment.
Addressing
Every communication tag has the same set of addressing properties. The meaning of each one depends on the protocol driver, and the page of each protocol explains how to fill them. As a quick reference:
| Property | Modbus | S7 (ISOTCP) | Melsec | West ASCII / IBox | Logix / S7CommPlus |
|---|---|---|---|---|---|
PLCStation |
Slave address (1–247) | – | Station number | Controller address | – |
PLCRack / PLCSlot |
– | CPU rack and slot | – | – | – |
MemFile_DB |
– | DB number (DB area) | – | – | – |
MemReadFunction |
Modbus read function (1, 2, 3, 4) | Memory area (1 = I, 2 = Q, 3 = M, 4 = DB…) | Device type (M, SM, L, X, Y, D…) | – | – |
MemWriteFunction |
Modbus write function (5, 6, 15, 16) | – | Device type (same code as read) | – | – |
MemAddress |
Register/coil address | Byte address | Device address | Parameter (West) / PID (IBox) | – |
MemSubElement |
– | – (bits: use TTagBit) |
– | – | – |
LongAddress |
– | – | – | – | Symbolic tag name in the PLC (Motor1.Speed, "DB10".Setpoint) |
Retries |
Attempts before declaring a failure (all drivers) |
The fastest way to get addressing right is the Tag Builder: right-click the protocol driver component (TModBusTCPDriver, TISOTCPDriver…) and choose Tag Builder. It creates tags already configured for that protocol.
ProtocolDriver is the property that links the tag to the driver. A tag without a driver does nothing — and raises no error.
Data type
The TagType property tells the driver how to interpret the bytes read from the device:
| TagType | Size | Interpretation |
|---|---|---|
pttDefault |
driver dependent | The protocol’s “natural size”: 16 bits on Modbus, 8 bits on S7, and so on. |
pttShortInt / pttByte |
8 bits | Signed / unsigned integer |
pttSmallInt / pttWord |
16 bits | Signed / unsigned integer |
pttLongInt / pttDWord |
32 bits | Signed / unsigned integer |
pttFloat |
32 bits | IEEE-754 floating point (REAL) |
pttInt64 / pttQWord |
64 bits | Signed / unsigned integer |
pttDouble |
64 bits | IEEE-754 floating point (LREAL) |
When the size of TagType differs from the protocol’s natural size the tag spans more than one memory: a pttFloat on Modbus takes two consecutive 16-bit registers. TagSizeOnProtocol (read-only) tells how many.
If the value arrives “scrambled” (a REAL that shows up as an absurd number, a DINT with its halves swapped) the device uses a byte order different from the one the driver assumes. Fix it with:
SwapBytes— swaps the two bytes of each 16-bit word.SwapWords— swaps the two 16-bit words of a 32-bit value.SwapDWords— swaps the two 32-bit words of a 64-bit value.
For Modbus, the most common setting for REAL on devices that use the “CDAB” order is SwapWords = True.
Value, scaling and limits
Numeric tags have two values:
ValueRaw— the value exactly as it came from the device.Value— the value after going through the chain of scales linked inScaleProcessor. With no scale,Value = ValueRaw.
HMI controls and your code normally use Value. To convert, say, the 0–27648 integer of a Siemens analog input into 0–100 %, link a TLinearScaleProcessor in ScaleProcessor — see Scale processors. Scaling works both ways: writing 50 to Value stores 13824 in the device.
MinValue / MaxValue, enabled by EnableMinValue / EnableMaxValue, bound what can be written to the tag. An assignment outside the range raises an exception (“value out of bounds”), fires OnWriteFail, and the value does not reach the device. The input controls (THMIEdit, THMITrackBar, THMIUpDown) honour these limits.
Events
The events below exist on every communication tag. All of them run on the main thread, so it is safe to touch visual controls inside them.
| Event | When it fires |
|---|---|
OnValueChangeFirst |
The value changed, before the dependent HMI controls are notified. Use it to prepare something the controls are about to show. |
OnValueChangeLast (or OnValueChange) |
The value changed, after the controls were notified. This is the “normal” value-change event. |
OnUpdate |
The tag was read successfully, even if the value did not change. Use it as a heartbeat or to log history at a fixed interval. |
OnReadOK / OnReadFail |
Result of each read. |
OnWriteOk / OnWriteFail |
Result of each write. |
OnAsyncValueChange |
A version of OnValueChange called on a driver-side thread, with no synchronization with the main thread. Use it only if you know what you are doing: it is faster, but it must not touch visual controls. |
To find out what went wrong on a failure, read LastSyncReadStatus, LastSyncWriteStatus, LastASyncReadStatus or LastASyncWriteStatus (type TProtocolIOResult: ioOk, ioTimeOut, ioIllegalFunction, ioIllegalRegAddress, ioDriverError, ioCommError, …).
Diagnostics
Each tag keeps counters that show in the Object Inspector at run time and help track down network problems: CommReadsOK, CommReadErrors, CommWritesOk, CommWriteErrors. AvgUpdateRate shows the real average interval between updates — if it is much larger than RefreshTime, the driver cannot keep up with the tag load and you should raise the RefreshTime of the less important tags or group them into blocks. ClockMonotonicTimeStamp holds the instant of the last update.
TagGUID is a unique identifier generated by the IDE for each tag. Do not edit it.
TPLCTagNumber
The most used tag: one memory, one value. Set ProtocolDriver, the addressing properties and TagType, link the HMI controls and you are done.
From code:
// Reading: the value is already in the tag, kept fresh by the scan. Speed := PLCTagNumber1.Value; // Writing: with AutoWrite = True the assignment already writes to the device. PLCTagNumber1.Value := 1500; // Forcing a synchronous read right now, regardless of the scan. PLCTagNumber1.Read; if PLCTagNumber1.LastSyncReadStatus = ioOk then ShowMessage(FloatToStr(PLCTagNumber1.Value));
TPLCBlock and TPLCBlockElement
TPLCBlock maps Size consecutive memories of the same TagType, starting at MemAddress. All of them are read and written in a single request, which guarantees the values are consistent with each other (same instant) and cuts traffic when the protocol has a high per-message overhead.
The values live in ValueRaw[index] (from 0 to Size-1) or in the ValuesRaw array. A TPLCBlock alone cannot be linked to an HMI control — that is what
TPLCBlockElement is for: a numeric tag whose PLCBlock property points to the block and whose Index says which element it represents. The element has everything a TPLCTagNumber has (Value, ScaleProcessor, limits, events) but no address of its own and no RefreshTime: the block does the communication.
To avoid creating the elements one by one, right-click the block and choose Map block elements… — the wizard creates one TPLCBlockElement per index.
Writing a block:
// With AutoWrite = True each assignment produces a write of one element. PLCBlock1.ValueRaw[3] := 10; // To write the whole block at once, turn AutoWrite off, // assign the values and call WriteDirect (synchronous) or WriteByScan (asynchronous). PLCBlock1.AutoWrite := False; PLCBlock1.ValueRaw[0] := 1; PLCBlock1.ValueRaw[1] := 2; PLCBlock1.ValueRaw[2] := 3; PLCBlock1.WriteDirect;
TPLCStruct, TPLCStructItem and TPLCStructString
TPLCStruct is a TPLCBlock whose TagType is fixed at pttByte: it reads Size consecutive bytes and lets each item decide how to interpret them. It is the way to map a structure with fields of different types — a Siemens DB mixing BOOL, INT, REAL and STRING, or a UDT.
The fields are represented by:
TPLCStructItem— a numeric field.PLCBlockpoints to the structure,Indexis the byte offset of the field inside it andTagTypegives the field type (the item spans the corresponding number of bytes).SwapBytes/SwapWords/SwapDWordsapply per item.
TPLCStructString— a text field.Indexis the offset,StringSizethe maximum length in characters,StringTypethe format (stCorstSIEMENS, seeTPLCStringbelow) andStringEncodingthe device’s code page.
Example — a Siemens DB with this layout:
| Offset | Type | Name |
|---|---|---|
| 0 | INT |
Counter |
| 2 | REAL |
Temperature |
| 6 | STRING[20] |
Product name (22 bytes including the Siemens header) |
becomes: a TPLCStruct with Size = 28; a TPLCStructItem with Index = 0, TagType = pttSmallInt; another with Index = 2, TagType = pttFloat; and a TPLCStructString with Index = 6, StringSize = 20, StringType = stSIEMENS.
The Map structure items… wizard (right-click the structure) creates the items from a list of types you assemble on screen, computing the offsets automatically.
As with blocks, AutoWrite = False + WriteDirect writes the whole structure in a single request.
TPLCString
Reads and writes a text from the device. The value is in the Value property (UTF8String), and THMIEdit/THMILabel show and edit text when linked to a TPLCString.
StringSize— maximum number of characters.StringType— how the string is stored in the device:stC— the characters run until a0byte is found (C terminator). Use it for Modbus, Melsec and Rockwell PLCs (pointingLongAddressto theDATAmember of theSTRING, e.g.MyString.DATA— which is what the Rockwell tag import wizard does).stSIEMENS— the S7STRINGformat: two header bytes (maximum length and used length) followed by the characters. The tag spansStringSize + 2bytes.stROCKWELL— reserved, not implemented yet; returns an empty string.
StringEncoding— the device’s code page (UTF_8,CP1252,CP850…). The tag converts to/from UTF-8 automatically.
OnAsyncStringChange is the string counterpart of OnAsyncValueChange.
TTagBit
Extracts a range of bits from another numeric tag (PLCTag), with no extra communication. StartBit is the least significant and EndBit the most significant bit of the range (both from 0, at most 31; EndBit >= StartBit). The TTagBit value is the range shifted right:
| Source tag value | StartBit | EndBit | TTagBit value |
|---|---|---|---|
5 (101b) |
0 | 0 | 1 |
5 (101b) |
0 | 2 | 5 |
5 (101b) |
1 | 2 | 2 (10b) |
5 (101b) |
2 | 2 | 1 |
Writing to a TTagBit works: it takes the current value of the source tag, changes only the bits in the range and writes the result back — so with AutoWrite = True the bit reaches the device.
UseRawValue selects whether the bits come from ValueRaw (True) or from Value (False, default). Turn it on when the source tag has a scale.
The typical use is a PLC status or command word where each bit has a meaning: one TPLCTagNumber reads the word and one TTagBit per bit feeds the THMICheckBoxes. The Map bits wizard (right-click any numeric tag) creates the 8, 16 or 32 TTagBits at once. The examples/laz_isotcp_mapping_bits_from_other_tag example shows this with a byte of a Siemens DB.
TNumericExprTag
A virtual numeric tag: its value is the result of Expression, evaluated whenever one of the tags linked to the variables A to J changes. It has no driver and no address.
Expression = 'A * B / 100'
Expression = 'ifthen(A > 80, 1, 0)'
Expression = 'sqrt(sqr(A) + sqr(B))'
The syntax is that of Free Pascal’s TFPExpressionParser (arithmetic and comparison operators, and/or/not, math functions, plus the ifthen(condition, ifTrue, ifFalse) function added by PascalSCADA). An error in the expression is reported in LastEvalutionError. It can have a ScaleProcessor. See the Numeric expression tag page for more examples.
Tags are TComponents, so they can be created from code — handy for applications that load their configuration from a database:
uses PLCTagNumber, ProtocolTypes; var t: TPLCTagNumber; begin t := TPLCTagNumber.Create(Self); t.Name := 'Tank1_Level'; t.MemReadFunction := 3; // Modbus: holding register t.MemWriteFunction := 16; t.MemAddress := 100; t.PLCStation := 1; t.TagType := pttFloat; t.SwapWords := True; t.RefreshTime := 500; t.ProtocolDriver := ModBusTCPDriver1; // link the driver last t.OnValueChange := @LevelChanged; end;
Link ProtocolDriver after setting the address: when it receives the driver, the tag registers itself in the driver’s scan with the address it has at that moment. To remove it, just t.Free — the tag unregisters from the driver and from the controls linked to it.
Related examples
examples/TagTypes— the same Modbus block read with everyTagType(pttBytetopttDouble) and theSwapBytes/SwapWordscombinations, withTPLCBlockElementandTPLCStructItemside by side; the best place to see the effect of each type.examples/laz_isotcp_mapping_bits_from_other_tag— onepttByteTPLCTagNumberand oneTTagBitper bit.examples/laz_numericexpr—TNumericExprTagadding two tags driven byTHMITrackBars.examples/laz_modbus_tcp_example—TPLCBlock+TPLCBlockElement,TPLCTagNumberand input controls over Modbus TCP.examples/laz_console_app— tags and a Modbus TCP driver in a console application, without the LCL (a datamodule and no forms).examples/hmi_bandeja—TPLCStructwithTPLCStructItemandTPLCStructStringmapping a Siemens DB.