Required knowledge
- Data communication;
- The physical medium your protocol will use (serial, TCP/IP, UDP);
- Component development in Delphi/Lazarus;
- The protocol being implemented — with the specification at hand, or at least traffic captures (Wireshark) from a real device.
Definitions
- Update scan: cyclic method that updates the tag value with the last value read by the protocol driver. It runs on a thread of the driver and delivers the values to the tags on the main thread.
- Read scan: cyclic method that sweeps the memory areas most in need of an update, encodes the data packet to send to your device, sends it through the communication port, waits for the port’s answer, receives the data, decodes it and updates the internal data areas with the value and the date/time of the last read.
- Write scan: cyclic method that serves the write orders queued by the tags (
ScanWrite, or an assignment toValuewithAutoWrite = True), executing them asynchronously — the application goes on while the write travels to the device, and the result comes later through the tag events. - Synchronous read: a read where the read scan is paused to free the communication port and the application reads the tag directly (
Tag.Read), blocking until the answer arrives. - Synchronous write: a write where the read scan is paused the same way and the application writes directly (
Tag.Write), blocking until the device confirms.
Introduction
Firstly, I’ll explain my idea of a protocol driver and how I implemented it, with small pieces of code as an example of each part. A protocol driver is the object that manages the tags in your application. It updates the tags respecting their scan rate, organizes them in blocks and avoids a memory being read twice (or more) in a single cycle. Its internal organization can vary from one protocol to another, which may read a single tag or a block of tags per request. Everything in the name of performance.
The tags in PascalSCADA are copies of values stored in another area, managed by the driver. It is through this internal area that the driver manages its read scan. The organization of this area varies with the device’s memory organization. The tags, in turn, may represent one or more memory addresses of your device.
What the base class TProtocolDriver already does for you:
┌──────────────────────── TProtocolDriver ────────────────────────┐
tags ──AddTag──▶ │ tag list │
│ │
│ TScanThread ──▶ DoScanRead ──▶ DoRead ──▶ port ──▶ device │
│ (your code: builds and decodes frames) │
│ │
│ TScanUpdate ──▶ DoGetValue ──▶ Synchronize ──▶ Tag.Value │
│ (your code: copies from the internal area)│
└─────────────────────────────────────────────────────────────────┘
- creates and keeps the two threads (
TScanThread, which callsDoScanReadin a loop, andTScanUpdate, which callsDoGetValuefor each tag and delivers the values on the main thread); - implements the
Read/Write/ScanRead/ScanWritecalled by the tags, pausing the scan and calling yourDoRead/DoWrite; - handles the synchronization between the threads (critical sections, scan pause) — you never need a mutex inside the
Do*methods; - handles the
CommunicationPortproperty,ReadOnly, the counters and the Object Inspector’sLiteralTagAddress.
What is left for you: seven methods describing your device and your protocol. That is what the rest of this page shows.
To demonstrate, I’ll use a fictitious PLC with a 16-bit register area and digital inputs and outputs addressed in bytes (8 bits), all areas supporting block read/write (update several tags in a single request), and simple PLC addressing from 1 to 255 (like Modbus).
Step 1: the unit and the device structure
The first step is to create a unit to hold your new protocol and add it to the PascalSCADA package (see Registering the driver below). In that unit, the representation of our fictitious PLC would be something like this:
uses ProtocolDriver, ProtocolTypes, PLCMemoryManager, Tag, PLCBlock, commtypes;
type
TDummyPLC = record
PLCAddress: Byte;
Inputs: TPLCMemoryManager; // represented by MemReadFunction = 1 in our tags
Outputs: TPLCMemoryManager; // represented by MemReadFunction = 2 in our tags
Registers: TPLCMemoryManager; // represented by MemReadFunction = 3 in our tags
end;
TDummyPLCs = array of TDummyPLC;
Note the class TPLCMemoryManager. What does it do? It organizes memories of the same area into continuous blocks as large as possible, avoiding duplicated memories and optimizing your communication. Two properties control its whole behaviour:
MaxHole: how many memories may be missing and still keep a single block. Say the addresses [1, 2, 5, 6] are added. WithMaxHole = 0two blocks are formed, [1, 2] and [5, 6]. WithMaxHole = 2a single block [1, 2, 3, 4, 5, 6] is formed. Addresses 3 and 4 are added to keep the block continuous, so it is read with a single request by the driver, improving performance.MaxBlockItems: the maximum block size. If [1, 2, 3, 4, 5, 6] are added withMaxBlockItems = 3, two blocks are formed, [1, 2, 3] and [4, 5, 6]. Useful for protocols that limit the request size, such as Modbus (125 registers per read).0means no limit.
The methods you will use on it:
| Method | Does |
|---|---|
AddAddress(Address, Size, RegSize, ScanTime) |
Registers Size memories starting at Address, with a scan of ScanTime ms. RegSize is the variable size relative to the smallest word of the area: to add MW0, MW2 and MW4 of a Siemens (smallest word = byte) use AddAddress(0, 3, 2, 1000). The resulting block gets the smallest ScanTime of the tags composing it. |
RemoveAddress(Address, Size, RegSize) |
The inverse. |
Blocks[i] |
The continuous blocks formed, each with AddressStart, Size, ScanTime, LastUpdate and NeedRefresh (true once the scan time has elapsed). |
SetValues(Address, Len, RegSize, Values, LastResult) |
Stores the values read from the device and stamps the time. |
SetFault(Address, Len, RegSize, Fault) |
Marks that the read failed — the tags receive the TProtocolIOResult and fire OnReadFail. |
GetValues(Address, Len, RegSize, Values, LastResult, Timestamp) |
Copies values, result and time to hand to a tag. |
Note the comment on each memory area. I chose the tag’s MemReadFunction property to select the data area (inputs, outputs and registers): 1 identifies the digital inputs, 2 the digital outputs and 3 the registers. Where this mapping is tied to the memory area comes a bit further on.
With the structure representing your device done, the second step is to create a class derived from TProtocolDriver:
type
TDummyProtocol = class(TProtocolDriver)
private
FPLCs: TDummyPLCs;
protected
procedure DoAddTag(TagObj: TTag; TagValid: Boolean); override;
procedure DoDelTag(TagObj: TTag); override;
procedure DoScanRead(Sender: TObject; var NeedSleep: LongInt); override;
procedure DoGetValue(TagRec: TTagRec; var values: TScanReadRec); override;
function DoRead(const tagrec: TTagRec; out Values: TArrayOfDouble; Sync: Boolean): TProtocolIOResult; override;
function DoWrite(const tagrec: TTagRec; const Values: TArrayOfDouble; Sync: Boolean): TProtocolIOResult; override;
public
destructor Destroy; override;
function SizeOfTag(aTag: TTag; isWrite: Boolean; var ProtocolTagType: TProtocolTagType): BYTE; override;
published
property ReadSomethingAlways;
end;
In this new protocol you must say how tags are added to the driver’s scan to be read. How? Simple. Override the method:
procedure DoAddTag(TagObj: TTag; TagValid: Boolean);
It adds tags to the memory area managed by the driver. Do the tag checks here (address range, tag class) and, if the tag is valid, call the inherited method with
inherited DoAddTag(TagObj, TheTagIsValid);
to add the tag to the base class so it gets updated at its scan rate. The second parameter matters: the base class marks the tag as valid or invalid, and an invalid tag stays in the list but is never read — that is what happens when the user fills in a MemReadFunction the driver does not know. Call inherited always, even with False; if you don’t, the tag is not registered and DoDelTag will not find it later.
In this example I’ll handle block tags only. With our fictitious PLC the method looks like this:
procedure TDummyProtocol.DoAddTag(TagObj: TTag; TagValid: Boolean);
var
Valid, plcFound: Boolean;
plc: Integer;
begin
Valid := False;
plcFound := False;
// as I said, only block tags are handled in this example.
if TagObj is TPLCBlock then
with TagObj as TPLCBlock do begin
// check whether the PLC address is in the accepted range (1 to 255)
// and, if so, whether that PLC is already registered in the
// memory area managed by the driver.
if PLCStation in [1..255] then
for plc := 0 to High(FPLCs) do
if FPLCs[plc].PLCAddress = PLCStation then begin
plcFound := True;
Break;
end;
// PLC not found: add it.
if (not plcFound) and (PLCStation in [1..255]) then begin
plc := Length(FPLCs);
SetLength(FPLCs, plc + 1);
FPLCs[plc].PLCAddress := PLCStation;
FPLCs[plc].Inputs := TPLCMemoryManager.Create;
FPLCs[plc].Outputs := TPLCMemoryManager.Create;
FPLCs[plc].Registers := TPLCMemoryManager.Create;
FPLCs[plc].Registers.MaxBlockItems := 125; // our protocol's limit
plcFound := True;
end;
// is the tag valid (bound to some area)?
if plcFound and (MemReadFunction in [1..3]) then
Valid := True;
// add the tag to the memory area managed by the driver
if Valid then
case MemReadFunction of
1: FPLCs[plc].Inputs.AddAddress(MemAddress, TagSizeOnProtocol, 1, RefreshTime);
2: FPLCs[plc].Outputs.AddAddress(MemAddress, TagSizeOnProtocol, 1, RefreshTime);
3: FPLCs[plc].Registers.AddAddress(MemAddress, TagSizeOnProtocol, 1, RefreshTime);
end;
end;
// add the tag to the base class
inherited DoAddTag(TagObj, Valid);
end;
TagSizeOnProtocol is the tag size in protocol words — a TPLCBlock with Size = 10 and TagType = pttFloat over 16-bit registers spans 20 words. The tag computes it from your SizeOfTag (step 7), which is why it, and not Size, goes to the manager.
Done: your tag is validated and added to the scan of your protocol driver. But this method does not read the tag values by itself. It could — but it would be inefficient when performance is the goal, because the base class does not know the driver structure: it would have to request tag by tag, and a duplicated tag (same memory of the same PLC) would be requested twice. For an improved scan routine, two more methods must be overridden.
procedure DoGetValue(TagRec: TTagRec; var values: TScanReadRec);
Remember that tags are copies of a memory area managed by the driver? This is the method that makes the copy. It is called by the update thread for each tag, at the tag’s rate. Implementing it is simple: look up the memory in the protocol’s internal organization. For our fictitious driver:
procedure TDummyProtocol.DoGetValue(TagRec: TTagRec; var values: TScanReadRec);
var
plc: Integer;
begin
// sweep the PLCs and, on the one requested, ask the block manager
// of the desired area for the tag values.
for plc := 0 to High(FPLCs) do
if FPLCs[plc].PLCAddress = TagRec.Station then
case TagRec.ReadFunction of
1: FPLCs[plc].Inputs.GetValues(TagRec.Address, TagRec.Size, 1, values.Values,
values.LastQueryResult, values.ClkMonotonicTStamp);
2: FPLCs[plc].Outputs.GetValues(TagRec.Address, TagRec.Size, 1, values.Values,
values.LastQueryResult, values.ClkMonotonicTStamp);
3: FPLCs[plc].Registers.GetValues(TagRec.Address, TagRec.Size, 1, values.Values,
values.LastQueryResult, values.ClkMonotonicTStamp);
end;
end;
TTagRec is a snapshot of the tag properties at request time: Station, Address, Size, ReadFunction, WriteFunction, File_DB, SubElement, Rack, Slot, Path (the LongAddress), UpdateTime, Retries and the CallBack that returns the result to the tag. DoGetValue, DoRead and DoWrite work with it — not with the tag object — because they run on the driver threads.
Step 4: the read scan — DoScanRead
Fine, but who reads the data from my device and updates those memory areas? This method does:
procedure DoScanRead(Sender: TObject; var NeedSleep: LongInt);
It is called in a loop by the scan thread to check whether some tag needs to be read, sweeping the memory area managed by the driver. At the end, tell the scan thread what was done through NeedSleep:
NeedSleep = 0: the thread carries on normally. Return 0 whenever the driver performed some I/O, since I/O acts as a “natural delay” and avoids high CPU usage.NeedSleep < 0: the scan thread forces a thread context switch (ThreadSwitch) and returns as soon as possible. You may return this whenever your driver did nothing.NeedSleep > 0: the thread sleepsNeedSleepmilliseconds. You may return this whenever your driver did nothing.
The most common mistake of a new driver is returning
0without having done any I/O: the scan thread becomes a tight loop and the CPU goes to 100 %. If there was nothing to read, return1(or the time until the next block is due).
The scan routine of our fictitious driver looks like this (note it uses DoRead, presented in the next step):
procedure TDummyProtocol.DoScanRead(Sender: TObject; var NeedSleep: LongInt);
var
plc, block: Integer;
tagrec: TTagRec;
ReadResult: TProtocolIOResult;
Values: TArrayOfDouble;
didSomething: Boolean;
begin
didSomething := False;
NeedSleep := 0;
// without an active port there is nothing to do: sleep a bit instead of spinning
if (PCommPort = nil) or (not PCommPort.ReallyActive) then begin
NeedSleep := 1;
Exit;
end;
// sweep the PLCs
for plc := 0 to High(FPLCs) do begin
// sweep the blocks formed from the digital inputs
for block := 0 to High(FPLCs[plc].Inputs.Blocks) do
// if the block needs an update...
if FPLCs[plc].Inputs.Blocks[block].NeedRefresh then begin
// fill the TTagRec fields that matter to the protocol (or to DoRead)
tagrec.Station := FPLCs[plc].PLCAddress;
tagrec.ReadFunction := 1;
tagrec.Address := FPLCs[plc].Inputs.Blocks[block].AddressStart;
tagrec.Size := FPLCs[plc].Inputs.Blocks[block].Size;
// read through DoRead
ReadResult := DoRead(tagrec, Values, False);
if ReadResult = ioOk then
FPLCs[plc].Inputs.SetValues(tagrec.Address, tagrec.Size, 1, Values, ReadResult)
else
FPLCs[plc].Inputs.SetFault(tagrec.Address, tagrec.Size, 1, ReadResult);
didSomething := True;
end;
// repeat the above for the digital outputs and the registers...
end;
if not didSomething then
NeedSleep := 1;
end;
Two refinements the PascalSCADA drivers make, worth it once the number of blocks grows:
- Read one block per call, the most overdue first. Instead of reading every due block at once (which delays the fast tags while the slow ones are read), the Modbus driver builds the list of all blocks, sorts it by lateness and reads only the first; the thread calls
DoScanReadagain right after. A 100 ms tag then never waits for twenty 5 s blocks. ReadSomethingAlways: when no block is due, reading the oldest one anyway keeps the connection alive and detects a dead device early. Publish the inherited property and honour it in your scan.
Step 5: reading from the device — DoRead
To avoid building request packets twice, override
function DoRead(const tagrec: TTagRec; out Values: TArrayOfDouble; Sync: Boolean): TProtocolIOResult;
because it performs the synchronous reads (requested by the tag’s Read) and the asynchronous ones (requested by the driver’s scan). Building the request packet and decoding the received packet with the memory values happens here. tagrec carries the tag information (device address, memory address), and Values receives the decoded values. The Sync parameter is no longer used.
The return is a TProtocolIOResult: ioOk, ioTimeOut, ioCommError (corrupted answer), ioIllegalFunction/ioIllegalRegAddress/ioIllegalValue (the device refused), ioPLCError, ioDriverError, ioNullDriver (no active port)… Pick the most specific one: it reaches the tag in LastSyncReadStatus and is what the user sees when diagnosing.
This is where the driver talks to the communication port. The port (TCommPortDriver, be it TSerialPortDriver or TTCP_UDPPort) knows nothing about the protocol — it only carries bytes — and offers a synchronous operation:
function IOCommandSync(Cmd: TIOCommand; // iocWrite, iocRead or iocWriteRead
BytesToWrite: Cardinal; ToWrite: BYTES;
BytesToRead: Cardinal; // how many bytes of answer to expect
DriverID, DelayBetweenCmds: Cardinal;
pkt: PIOPacket; // result
OnBegin: TNotifyEvent = nil; OnEnd: TNotifyEvent = nil): Cardinal;
The returned TIOPacket carries WriteIOResult/ReadIOResult (iorOK, iorTimeOut, iorPortError…), Received and BufferToRead. Since a port may be shared by several drivers, wrap the transaction in PCommPort.Lock(DriverID) / Unlock(DriverID) — DriverID is a unique number the base class already gave your driver. The pattern every PascalSCADA driver follows:
function TDummyProtocol.DoRead(const tagrec: TTagRec; out Values: TArrayOfDouble;
Sync: Boolean): TProtocolIOResult;
var
request: BYTES;
pkt: TIOPacket;
remaining: LongInt;
begin
Result := ioNullDriver;
if (PCommPort = nil) or (not PCommPort.ReallyActive) then Exit;
request := BuildReadRequest(tagrec); // your protocol: header, function, address, CRC...
PCommPort.Lock(DriverID);
try
// 1) send the request and read the answer header (fixed size)
if PCommPort.IOCommandSync(iocWriteRead, Length(request), request, HEADER_SIZE,
DriverID, 0, @pkt) = 0 then begin
Result := ioDriverError;
Exit;
end;
if pkt.ReadIOResult = iorTimeOut then begin Result := ioTimeOut; Exit; end;
if pkt.ReadIOResult <> iorOK then begin Result := ioCommError; Exit; end;
// 2) the header says how many bytes are still coming: read the rest
remaining := RemainingBytes(pkt.BufferToRead);
if remaining > 0 then begin
if PCommPort.IOCommandSync(iocRead, 0, nil, remaining, DriverID, 0, @pkt2) = 0 then ...
pkt.BufferToRead := ConcatenateBYTES(pkt.BufferToRead, pkt2.BufferToRead);
end;
// 3) validate (CRC, function echo, exception code) and convert to Double
Result := DecodeAnswer(pkt.BufferToRead, tagrec, Values);
finally
PCommPort.Unlock(DriverID);
SetLength(request, 0);
SetLength(pkt.BufferToRead, 0);
end;
end;
The two-step read — fixed-size header, then the rest — is what lets the driver know how many bytes to expect without guessing; a fixed-size protocol needs a single call. If the answer comes from another function or another station (noise on a serial line), drain the port with 1-byte iocReads until a timeout, as Modbus does, otherwise the next request reads the leftovers.
The values in Values are always Double, one protocol word per position: for a block of 4 16-bit registers, Values has 4 elements in 0..65535. The tag is the one assembling pttFloat, pttLongInt etc. from those words, using the size you reported in SizeOfTag — the driver does not convert types.
Separate frame building from the I/O flow. The Modbus and Melsec drivers put the flow above in a family base class and leave only two virtual methods to the subclasses, EncodePkg (TTagRec → bytes) and DecodePkg (bytes → values + SetValues/SetFault). That is how TModBusRTUDriver and TModBusTCPDriver share 90 % of the code and differ only in header and CRC. Do the same from the start if your protocol has serial/TCP variants.
Step 6: writing to the device — DoWrite
I can read my tags; how do I write values to the device? DoWrite is for that — override it, build the packet and send it:
function DoWrite(const tagrec: TTagRec; const Values: TArrayOfDouble; Sync: Boolean): TProtocolIOResult;
This is the method performing the synchronous writes (tag with AutoWrite = False and a later call to Write) and the asynchronous ones (a value assigned to Value with AutoWrite = True). tagrec carries the tag information (device address, memory address — use WriteFunction, not ReadFunction), and Values the values to write. The Sync parameter is no longer used.
The flow is the same as DoRead: build, Lock, IOCommandSync, validate the confirmation, Unlock. After a successful write, also update the internal area with SetValues — so other tags pointing to the same memory show the new value before the next scan. If the driver has ReadOnly = True, the base class already refuses the write with ioReadOnlyProtocol before it gets here.
Step 7: word sizes — SizeOfTag
But my device has registers as words while digital inputs and outputs are addressed as bytes. How do I say that? Simple. Tags do a lot of type conversions, but the protocol must tell what kind of data it is providing to the tag so it can convert. Override
function SizeOfTag(aTag: TTag; isWrite: Boolean; var ProtocolTagType: TProtocolTagType): BYTE;
which reports the size in bits of the word the tag references and its type (ptBit, ptByte, ptShortInt, ptWord, ptSmallInt, ptDWord, ptLongInt, ptFloat, ptInt64, ptQWord, ptDouble). Return the size in Result and the type in ProtocolTagType. isWrite allows different sizes for reads and writes. In our fictitious driver (again block tags only; the other tag classes are up to you), assuming digital inputs and outputs are bytes and registers are words:
function TDummyProtocol.SizeOfTag(aTag: TTag; isWrite: Boolean;
var ProtocolTagType: TProtocolTagType): BYTE;
begin
Result := 0;
ProtocolTagType := ptUnknown;
if aTag is TPLCBlock then
case TPLCBlock(aTag).MemReadFunction of
1, 2: begin
Result := 8;
ProtocolTagType := ptByte;
end;
3: begin
Result := 16;
ProtocolTagType := ptWord;
end;
end;
end;
The tag consults this value when computing TagSizeOnProtocol and when assembling TagTypes larger than the protocol word (two 16-bit registers become one pttFloat). If you report 16 bits but deliver bytes in Values, the values come out wrong.
I’ve read enough. I want to delete my tags, close this page and leave… Easy: for your tag to be deleted and removed from the driver’s scan, override one last method:
procedure DoDelTag(TagObj: TTag);
Override it to remove tags from the driver’s scan. Don’t forget to call the inherited method,
inherited DoDelTag(TagObj);
to remove the tag from the base class. The code is very similar to DoAddTag, except that the tag is removed from the area managed by the driver (RemoveAddress with the same parameters as AddAddress). It is called when the tag is destroyed, when it changes ProtocolDriver and — importantly — whenever any addressing property changes: the tag removes itself with the old address and adds itself again with the new one. That is why DoAddTag/DoDelTag must be symmetrical.
In the driver’s destructor, free the TPLCMemoryManagers you created.
Keep in mind that your driver needs a communication port set and active for the tags to be updated. This is a condition for the protocol driver to update the tags.
Registering the driver
With the seven methods written, the driver still has to show up on the palette:
- Unit in the package: add the unit to
pascalscada.lpk(or to your own package depending onpascalscada). - Palette registration: in
src/scada_dsng/scadareg.pas, include the class in theRegisterComponents(strProtocolsPallete, [...])call. In your own package, write aprocedure Registerwith the same call. - Icon: a 24×24 PNG named
TDummyProtocol.pnginartwork/24x24png/(and the SVG inartwork/scalable/); runartwork/generateres.shto regenerate the resource file. - Tag Builder (optional): the wizard that creates tags from the driver’s context menu. Since it has forms (LCL), it lives in the design package (
scada_dsng), not in the driver unit: the driver exposesHasTabBuilderEditor/OpenTagEditorand a globalSetTagBuilderToolFor…ProtocolFamilythat the design package fills at initialization — seemodbustagassistant.pasandsiemenstagassistant.pasas models. Without it the driver works normally, it just lacks the menu item. LiteralTagAddress(optional): override it so the Object Inspector shows the address in your protocol’s notation (DB5.DBW20,40001) in the tag hint.
Testing without the device
You don’t need a PLC to develop the driver: the test suite has a fake port (tests/testsupport.fakeport.pas, TFakeCommPort) that records what the driver wrote and replays queued answers. A read test looks like this (adapted from tests/ut.modbustcp.pas):
// DoRead is protected: a "probe" exposes it to the test and disables the
// scan thread, so that only the test uses the fake port.
type
TDummyProtocolProbe = class(TDummyProtocol)
protected
procedure DoScanRead(Sender: TObject; var NeedSleep: LongInt); override; // NeedSleep := 1
public
function ReadSync(const aTag: TTagRec; out aValues: TArrayOfDouble): TProtocolIOResult;
end;
function TDummyProtocolProbe.ReadSync(const aTag: TTagRec; out aValues: TArrayOfDouble): TProtocolIOResult;
begin
Result := DoRead(aTag, aValues, True);
end;
procedure TTestDummyProtocol.SetUp;
begin
FPort := TFakeCommPort.Create(nil);
FPort.Active := True;
FDrv := TDummyProtocolProbe.Create(nil);
FDrv.CommunicationPort := FPort;
end;
procedure TTestDummyProtocol.AReadGoesOutAndBackThroughThePort;
var
res: TProtocolIOResult;
vals: TArrayOfDouble;
begin
// what the "device" would answer
FPort.QueueResponse(BytesOf('01 03 04 00 0A 00 14'));
res := FDrv.ReadSync(TagRecFor(1, 3, 16, 0, 2), vals); // station, read function, write function, address, size
AssertEquals('result', Ord(ioOk), Ord(res));
AssertBytesEqual('the request that went out', BytesOf('01 03 00 00 00 02'), FPort.LastWrittenFrame);
AssertEquals('two values', 2, Length(vals));
AssertEquals('first register', 10, vals[0], 0);
AssertEquals('answer fully consumed', 0, FPort.PendingResponses);
end;
TagRecFor, BytesOf and AssertBytesEqual come from tests/testsupport.protocol.pas and tests/testsupport.bytes.pas. QueueTimeout simulates a silent device, to test the ioTimeOut path; WrittenFrame(i) inspects each request when the driver makes several exchanges per read. The tests run with tests/pascalscada_tests.lpi. Write one test per protocol function and one per error code before connecting to the real device — almost every driver defect (swapped byte, wrong size, CRC) shows up here, in seconds, with the expected frame next to the one that went out.
Common mistakes
| Symptom | Cause |
|---|---|
| Tags never update and never flag a fault | DoAddTag did not call inherited with True, or DoScanRead never calls SetValues/SetFault. |
| CPU at 100 % | DoScanRead returns NeedSleep = 0 without having done I/O. |
| A second driver on the same port hangs | Lock without Unlock on an error path — use try…finally. |
| Wrong values only on 32-bit types | SizeOfTag reports a size different from what Values delivers. |
| Tag drops out of the scan when its address changes | DoDelTag does not remove with the same parameters DoAddTag added. |
| The next read returns garbage after an error | The port was not drained after an unexpected answer. |
Failures show up as a generic ioDriverError |
DecodePkg does not tell timeout, CRC and device exception apart. |
I hope I managed to explain how drivers work in PascalSCADA. Criticism, suggestions, improvements and above all corrections: use the comments.
Reference drivers in the repository
All in src/scada/, from the simplest to the most complete:
iboxdriver.pas—TIBoxDriver: serial, a few fixed registers per station, no memory manager; the smallest complete example of the seven methods.westasciidriver.pas—TWestASCIIDriver: a serial ASCII protocol with checksum.modbusdriver.pas+modbusserial.pas+modbustcp.pas— the Modbus family: base with the I/O flow and oneTPLCMemoryManagerper area, subclasses withEncodePkg/DecodePkgfor RTU and TCP. The recommended model.MelsecDriver.pas+MelsecTCP.pas— the same family structure, with ten memory areas.s7family.pas+isotcpdriver.pas— a protocol with connection and negotiation (PDU), several areas and per-DB blocks.lgxdriver.pas— EtherNet/IP: symbolic addressing throughLongAddress, no per-address memory manager.
The matching tests in tests/ut.*.pas show, frame by frame, what each one sends and expects.